Steam & Boilers
Saturated Steam Tables: Reading Temperature, Pressure and Enthalpy
Exam reference: SG-0004 (the label exam questions use for this figure)
What the figure shows
Two tables side by side. The first lists saturated steam by temperature, 32 to 400 F, with absolute pressure and enthalpy of liquid, of evaporation and of vapor in BTU per pound. The second lists the same enthalpy columns by absolute pressure, 0.5 to 400 psi, with the matching temperature.
How to read it
- Pick the table by what you are given: enter the pressure table when the question gives a pressure.
- The tables use absolute pressure, so add 14.7 to a gauge reading before you look it up.
- Latent heat of vaporization is the enthalpy of evaporation column, not the liquid or vapor column.
What exam questions ask
- What is the latent heat of vaporization for a boiler at 135.3 psig? Convert to 150 psia, then read the evaporation column: 863.6 BTU per pound.
- What is the superheater outlet temperature when saturated steam at 400 psia gains a given superheat? Read the saturation temperature, 444.59 F, and add the superheat, giving 637.42 F.
Common mistakes
- Reading gauge pressure straight into the table: the tables list absolute pressure, so atmospheric pressure must be added first.
- Stopping at the saturation temperature or the superheat alone: the outlet temperature is the sum of the two.
Related figures
Steam & BoilersWater Heating Curve: Temperature vs. BTU
Steam & BoilersMarine D-Type Boiler Cutaway, Parts A to K
Steam & BoilersCondenser Vacuum vs. Steam Temperature Table
Engineering SafetyGlass Bulb Sprinkler Head Cross Section
Engineering SafetySmoke and Air Flow in a Shipboard Fire
General EngineeringLimit Sensor Assembly Drawing and Ports